After-sales Service Total Heat Exchanger

Maintenance Details

Maintenance and Inspection Guidelines for Standalone Total Heat Exchanger

Part name Periodic inspection Preventive maintenance
Part category Part name Inspection details Inspection methods Judgment criteria <Guideline> Maintenance details Inspection cycle Replacement cycle
1 year Others Hours of use Years of use
Standalone Total Heat Exchanger 1 Heat exchange element Rotating type Check for clogging and damage Visual inspection No clogging or damage Cleaning or replacement 10 years
Static type Check for clogging and damage Visual inspection No clogging or damage Cleaning or replacement 10 years
2 Filter (non-woven) Check for dirt, clogging, and tears Visual inspection No significant dirt, clogging, or tears Cleaning or replacement Monthly 1 year
3 Air seal (rotating type) Check for gaps and tears Visual inspection No gaps or tears Replacement 3 years
4 V-belt (rotating type) Check for wear and scratches Visual inspection No significant wear, scratches, or cracks Replacement 5 years
5 Geared motor (rotating type) Check for operating noise
Measuring insulation resistance
Auditory inspection, 500 V megger Abnormal noise
1 MΩ or greater
Replacing if bearing noise is loud
Replacing if insulation is deteriorated
10000 Hr
6 Boss(rotating type) Check for operating noise and vibration Auditory and visual inspection Abnormal noise and abnormal vibration Lubrication or replacement 15000 Hr
7 Exterior Check for appearance Visual inspection No paint peeling, rust, or corrosion Repair painting or replacement 15 years

Maintenance and Inspection Guidelines for Total Heat Exchange and Ventilation Unit

Part name Periodic inspection Preventive maintenance
Part category Part name Inspection details Inspection methods Judgment criteria <Guideline> Maintenance details Inspection cycle Replacement cycle
1 year Others Hours of use Years of use
Total Heat Exchange and Ventilation Unit 1 Heat exchange element Rotating type Check for clogging and damage Visual inspection No clogging or damage Cleaning or replacement 10 year
Static type Check for clogging and damage Visual inspection No clogging or damage Cleaning or replacement 10 year
2 Filter Check for dirt, clogging, and tears Visual inspection No significant dirt, clogging, or tears Cleaning or replacement Monthly 1 year
3 Electric motor Fan motor Check for operating noise
Measuring insulation resistance
Auditory inspection, 500 V megger No abnormal noise

1 MΩ or greater
Replacing if bearing noise is loud
Replacing if insulation is deteriorated
20000 Hr
4 Geared motor (rotating type) 10000 Hr
5 Bypass damper
(including geared motor)
Check for operation
Check for dust
Visual inspection No abnormal operation
No dust
Replacement if there are operational issues
Cleaning
13 years
6 Electrical components Circuit board Check for dust Visual inspection No significant dust Cleaning 25000 Hr
Terminals Check for loose terminals, wire contacts, and dust Tightening up
Visual inspection
No loose terminals, wire contact issues, or dust Tightening up if terminals are loose
Re-insertion Clean if there is dust
13 years
Connectors Check for disconnected pins
Check for dust
Visual inspection No disconnected pins
No dust
Replacement
Cleaning
13 years
7 Humidifier Membrane type Check for dirt and leaks Visual inspection No significant dirt and no leaks Washing or replacement 5 years
Drip evaporation type Check for dirt Visual inspection No significant dirt Washing or replacement 3 years
Pressure reducing valve Check leaks Visual inspection No leaks Replacement 13 years
Solenoid valve Check for operation Auditory inspection No abnormal operation Replacement 13 years
Strainer Check for dust Visual inspection No dust Washing or replacement 5 years
Drain pan Check for leaks, corrosion, deterioration, clogs, peeling paint, cracks, and water flow Visual inspection No leaks, corrosion, deterioration, clogs, peeling paint, or cracks
Able to drain water
Washing or replacement 13 years
Float switch Check for operation Visual inspection No abnormal operation Replacement 5 years
Supply tank Check for dirt, corrosion, deterioration, debris Visual inspection No dirt, corrosion, deterioration, debris Washing or replacement 13 years
8 Exterior panel Check for appearance and insulating material Visual inspection No significant rust or corrosion
No insulating material peeling
Repairing 13 years
9 Remote control switch Check for appearance, display, and controllability Visual inspection No damage, display issues, or operational issues Replacement 13 years

Remarks
1) If the equipment falls under the category specified by laws and regulations, e.g., the Act on Maintenance of Sanitation in Buildings, please perform maintenance and inspection accordingly.
2) Operating hours are estimated based on 10 hours per day and 2500 hours per year. Confirm when entering the maintenance contract, as actual hours may vary.
3) The expected lifespan requiring product replacement is 13 – 15 years. The holding period for functional parts is at least six years after production ends.
4) The above conditions assume a general office building.
5) Please have a specialized contractor handle the maintenance of electrical components.
6) The above maintenance periods are general guidelines and may require special consideration based on usage, installation conditions, and water quality.

Source: Quoted from the Japan Refrigeration and Air Conditioning Industry Association’s recommended periodic maintenance and inspections.